According to ISO 9705 of building materials fire prevention performance standards, this fire test machine control platform provides independent gas analysis, including heat release rate and other related test required for related instruments, such as paramagnetic oxygen sensor, CO2/CO measuring instrument, He-Ni laser smoke density measurement and control system, etc.
Full-scale room corner test methods for surface of the article use the same principle with the cone calorimeter and SBI testmethod thatis based on the oxygen consumption. The method is to simulate the corner of the fire scene as a standard testconditions, and installation of a test sample entirely according to actual use, the test results apply only to specific sample installation, it is one of the most reliable standard test methods. In the corner fire test, in accordance with the requirements of ISO 9705, and the measured material mounted on the inner walls of the room (at the top is not installed).Using propane burners as a radiation source, the measurement of heat release rate, temperature, heat release, flashover time, CO2 /CO and other parameters, for which the most important is the heat release rate and the flashover time.
The test room is built by the density of 700kg / m³-A1 class fireproof material.
The internal dimensions of the room 3.6M X 2.4M X 2.4M.
The gate size: 0.8M (W) X2.0M (H).
Sandbox burner with propane gas and equipped with emergency shut-off devices.
Automatic ignition system to automatically record experimental data.
Independently movabletimetto display units.
10kV spark ignition, a cease-fire with safety devices. Fire extinguishing drainage system design.
The full scale room corner tester is equipped withstaircasefor easy maintenance exhaust pipes.
1, Full Scale Room Corner Combustion Tester adopts 0.5W HE-NE laser source.
2, Thorlabs optically detector.
3, Motor driven 5 class automatically calibration device with of 0%, 25%, 50%, 75%, 100% transmittance filters.
4, Full Scale Room Corner Combustion Tester adopts one touch calibration system in software with digital and curve display.
1, 16 bit data acquisition module is adopted by Full Scale Room Corner Combustion Tester.
2, Digital communication between computer and DAQ module.
3, Labview based application software on DAQ and data analysis.
1, Labview based application system,easilyand precise to operate and control.
2, Test status, calibration status display on screen.
3, Device status are displayed on screen and indicators onpanel.
4, Transducers data, process parameters, test result displayed onscreenvia digital and curve.
5, Test and calibration procedure auto executed by PLC program.
6, Full Scale Room Corner Combustion Tester can be controlled via both application screen and control panel.
7, PC and PLC communicate with digital protocol which is safe and robust.
1,Paramagn eticoxygen analyzer, the concentration range is 0~25%, an oxygen analyzer islinearresponse, Britain Servomex oxygen sensor; 10% to 90% response time of less than 12s; output noise does not exceed 50ppm;Reproduce the measured values lower than 100ppm,
2, Infrared CO2 analyzer range: 0 to 10%;accuracy of ± 0.01%;
3, The compressor works: cold trap: 0 to 5 degrees;
4, Import diaphragm pump, flow rate: 33 l / min
5, The standard detector color accuracy ± 5%, output linearity (transmission) <1%, absolute permeability <1%;
Test Data
1, Heat Release Rate (HRR),
2, Total Heat Release (THR),
3, Efficiency Heat Release (EHR),
4, Smoke Production Rate (SPR),
5, Time to Ignite (TTI),
6, Time to flameout,
7, Oxygen Consumption Rate,
8, CO2 Production Rate,
9, CO Production Rate(optional)
Size | 11,725(W)x4,000(D)x4,750(H)mm |
Console Size | 600(W)×750(D)×1800(H)mm |
Power supply | AC 220V, 50/60Hz, 15A (control), AC 380V, 60Hz, 50A(drive) |
Weight | About 7,500kg(Cabinet), 130kg(Control panel) |
Exhaust | Minimum 3.5m2/s(Measuring), Minimum 300m2/min(Exhaust) |
Other requirements | CO(0.8%)/CO2(8%), Compressed gas, Vacuum cleaners, Computers, Propane gas, Heptane gas, Nitrogen |